8,500 SF
Architect — HOK

Data Center: 8,500 sf data center served by multiple water-cooled CRAHUs with 3 dry-coolers on low roof adjacent in N+1 configuration. CRAHU air distribution is through raised floor with return through ceiling grilles to plenums directly connected to CRAHUs. The UPS capacity is 500 kVa, in a parallel redundant configuration with two 225 kVa modules and a space for a future module and a 500 kVa parallel redundant module. The UPS, cooling systems, lighting and select other systems are supported by a 1500 kW diesel generator with 24-hour fuel capacity. The fire suppression system is double interlocked pre-action system.